Mechanical Engineering / Makina Mühendisliği

Permanent URI for this collectionhttps://hdl.handle.net/11147/4129

Browse

Search Results

Now showing 1 - 2 of 2
  • Article
    Citation - WoS: 1
    Performance Analysis of Thermal Storage Assisted Cooling Tower With Night Cooling
    (Gazi Üniversitesi, 2020) Ouedraogo, Kiswendsida Elias; Toprak, Kasım
    As global warming and water scarcity issues continue to grow, it is essential to increase resources efficiency for air conditioners and power plants. In order to increase the efficiency, the systems need to be modified to take the advantages of the low night temperature and thermal storage tanks. In this study, the low night temperature and thermal storage tanks effects on the cooling tower is studied using TRNSYS. Using a chiller operating from 8:00 to 16:00 as a case study, hot water from the condenser is partially stored on daytime and cooled slowly during the night. The storage tank volume is optimized by considering two big tanks and five small tanks. The results show that night cooling reduces cooling water temperature by 5.8 degrees C or 21.8% while the cooling efficiency is increased by 36%. The thermal storage tanks enable to have the low continuous flow rate and help to reduce the fan power by 67.1%. On the storage side, compared to two tanks system, the tanks volume is reduced by 16.5% when 5 tanks are used. In theory this reduction can go up to 50% by increasing the number of tanks and reducing their individual size.
  • Article
    Citation - WoS: 6
    Citation - Scopus: 5
    Effect of Storage Tanks on Solar-Powered Absorption Chiller Cooling System Performance
    (Wiley, 2020) Toprak, Kasım; Ouedraogo, Kiswendsida Elias
    Thermal storage, low power tariff at night, and low nocturnal temperature can be used in synergy to reduce the cooling costs of the solar-powered absorption chiller cooling systems. This study aims to reduce the required cooling capacity of an absorption chiller (ACH) powered by a solar parabolic trough collector (PTC) and a backup fuel boiler by integrating thermal storage tanks. The thermal performance of the system is simulated for a building that is cooled for 14 h/day. The system uses 1000 m(2) PTC with 1020 kW ACH. Chilled water storage (CHWS) and cooling water storage (CWS) effects on the system performance for different operation hours per day of the ACH under Izmir (Turkey) and Phoenix (USA) weather conditions are analyzed. When the ACH operates 14 h/day as the load for both systems and both locations, the variations of the solar collector efficiency and the cooling load to heat input ratio remain less than 4% after the modifications. From the addition of CHWS to the reference system, a parametric study consisting of changing the ACH operation hours per day shows that the required cooling capacity of the ACH can be reduced to 34%. The capacity factor of the ACH is improved from its reference value of 41% up to 96%.