TR Dizin İndeksli Yayınlar / TR Dizin Indexed Publications Collection

Permanent URI for this collectionhttps://hdl.handle.net/11147/7149

Browse

Search Results

Now showing 1 - 4 of 4
  • Article
    Citation - WoS: 7
    Citation - Scopus: 8
    Update for Reactive Transport Modeling of the Kızıldere Geothermal Field To Reduce Uncertainties in the Early Inspections
    (TÜBİTAK - Türkiye Bilimsel ve Teknolojik Araştırma Kurumu, 2023) Erol, Selçuk; Akın, Taylan; Akın, Serhat
    The development of carbon capture and storage techniques has become essential to reduce and mitigating CO2 emissions to the atmosphere. CarbFix1 and CarbFix2 projects carried out in Iceland demonstrated that the emissions of waste CO2 gas from geothermal power plants can be captured and mixed with the effluent geofluid and subsequently injected back into the geothermal reservoir. This experience gained in the CarbFix projects expanded into other geothermal fields around Europe, and one of the demonstration sites is the geothermal field in Turkey, Kızıldere. This paper focuses on the results of an updated study on early field evaluations with reactive transport simulations. In the new three-dimensional numerical model, the geological formations and fault zones were updated according to the well-logs data. Based on the tracer tests performed in the field, the anisotropic permeabilities between the wells were evaluated and imposed into the model. Geofluid chemistry, mineral components, and the volume fractions used as input in the simulations are modified depending on the performed laboratory experiments on the metamorphic schists taken from the geothermal site (i.e. X-ray diffraction (XRD), energy dispersive X-ray (EDX), scanning-electron microscope (SEM), and batch reactor tests). Different thermodynamic databases such as Lawrance Livermore National Laboratory (LLNL) and Thermoddem databases were tested using PHREEQC and TOUGHREACT programs for consistency with experiments. The thermodynamic conditions and the geofluid-rock-CO2 interactions prevent the mineralization of CO2 in the reservoir. This outcome differs from CarbFix projects in terms of the carbonization process, but the CO2 injection is still reliable with solubility-trapping in a geothermal reservoir to partially mitigate the emission. Roughly, 200 kt of CO2 in 10 years can be safely injected into the geothermal reservoir. According to the new analysis, the ratio of magnesium, sodium, and potassium varies in solid solution series of feldspars and clay minerals as albite end-member and montmorillonite/illite end-members, respectively. The evaluations of solid solution reactions are relatively limited in the law of mass action approach used by PHREEQC and TOUGHREACT. © TÜBİTAK.
  • Article
    Citation - WoS: 1
    Performance Analysis of Thermal Storage Assisted Cooling Tower With Night Cooling
    (Gazi Üniversitesi, 2020) Ouedraogo, Kiswendsida Elias; Toprak, Kasım
    As global warming and water scarcity issues continue to grow, it is essential to increase resources efficiency for air conditioners and power plants. In order to increase the efficiency, the systems need to be modified to take the advantages of the low night temperature and thermal storage tanks. In this study, the low night temperature and thermal storage tanks effects on the cooling tower is studied using TRNSYS. Using a chiller operating from 8:00 to 16:00 as a case study, hot water from the condenser is partially stored on daytime and cooled slowly during the night. The storage tank volume is optimized by considering two big tanks and five small tanks. The results show that night cooling reduces cooling water temperature by 5.8 degrees C or 21.8% while the cooling efficiency is increased by 36%. The thermal storage tanks enable to have the low continuous flow rate and help to reduce the fan power by 67.1%. On the storage side, compared to two tanks system, the tanks volume is reduced by 16.5% when 5 tanks are used. In theory this reduction can go up to 50% by increasing the number of tanks and reducing their individual size.
  • Article
    Citation - WoS: 7
    Inertia and Droop Controller for a Modern Variable Speed Wind Turbine To Provide Frequency Control in a Microgrid
    (Gazi Üniversitesi, 2020) Hassan, Ali; Altın, Müfit; Bingöl, Ferhat
    The increasing penetration of modern Variable Speed Wind Turbines (VSWTs) in microgrids creates the problem of frequency stabilization due to reduced inertia of the power system. To emulate the Inertia Response of the conventional synchronous machines, wind turbines can be provided with an inertia emulation controller. The modeling presented in this paper aims at equipping the modern Type D wind turbine with inertia response and primary frequency control (PFC) capabilities. Two controllers - inertial and droop, are implemented and their frequency control capabilities are compared in an isolated power system which consists of a conventional steam turbine generator and a wind farm. The results suggest that proposed controllers help in better frequency control performance in the microgrid.
  • Article
    Citation - WoS: 7
    Citation - Scopus: 7
    The Importance of Internal Heat Gains for Building Cooling Design
    (Yıldız Teknik Üniversitesi, 2017) Coşkun, Turgay; Turhan, Cihan; Durmuş Arsan, Zeynep; Gökçen Akkurt, Gülden
    This paper aims to investigate the effect of internal heat gains on the cooling load of a building. The house occupied by three adult men is selected as the case study for paper. The house is in the third floor of the apartment. The apartment has four flats and it has no insulation around the external walls. The heat dissipation from lighting devices, electrical equipment and the occupants are calculated by using the DesignBuilder v4 Beta release simulation program. The temperature of the house is observed during three weeks by using hobo data loggers and calibration of the measurements is made with respect to weather data file of the flat. Detailed schedule based on time of operation and occupancy is prepared to get more accurate results. Annual energy consumption and cooling load of the house is determined by using the dynamic simulation program.