Optimizing Thermal Comfort in Physical Exercise Spaces: A Study of Spatial and Thermal Factors
Loading...
Date
2024
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
Elsevier
Open Access Color
Green Open Access
Yes
OpenAIRE Downloads
OpenAIRE Views
Publicly Funded
No
Abstract
Fitness centers have become famous for maintaining a healthy lifestyle. They require different thermal comfort conditions and higher fresh air supply rates than other indoor spaces. However, even well-designed centers may cause discomfort due to factors such as design decisions, ventilation, overheating, and overcrowding. The standards for fitness centers do not consider these specific requirements sufficiently, so this study focuses on understanding the thermal comfort requirements during physical exercise and evaluating spatial and thermal factors affecting the thermal environment around the body. The study investigated the ceiling height, lateral and frontal distances between machines, and vent locations as spatial factors and inlet temperature and air velocity as thermal factors. A thirty-minute moderate-intensity constant work rate exercise test was conducted in a controlled climatic chamber using a cycle ergometer with six healthy male participants. The experiment conditions were simulated in CFD software using the collected data. Once a validated simulation model was provided, computational models for different environmental and spatial scenarios for the five-person cycling class were generated. Using Taguchi L9 (34) orthogonal arrays method, nine spatial scenarios were simulated with three different thermal operations each. Optimal factor levels were determined by using thermal comfort conditions (based on predicted mean vote) around the body's thermal plume. The results showed that a ceiling height of 5 m, lateral and frontal distances of 1 m and 0.5 m between machines, and Type 2 (two inlets mounted on the ceiling) ventilation strategy were optimal for achieving better thermal comfort values in a thermal condition of 18 °C and 0.2 m·s−1. The study found that increasing the ceiling height and using cross-positioned vents that project air vertically from the ceiling improved the comfort conditions significantly. It is expected that these criteria, which were determined, compared with the standards and detailed, will contribute to the production processes of comfortable exercise spaces. © 2023 Elsevier B.V.
Description
Keywords
Cfd, Fitness Centers, Orthogonal Arrays, Physical Exercise, Taguchi L9, Thermal Comfort, Fitness centers, Comfort conditions, Taguchi L9, Fresh air, Taguchi l9, Air, Fitness center, Physical exercise, Thermal comfort, Thermal factors, Spatial factors, Ceiling height, Orthogonal arrays, Orthogonal array, Ceilings, CFD, Healthy lifestyles, Sports
Fields of Science
Citation
WoS Q
N/A
Scopus Q
N/A

OpenCitations Citation Count
N/A
Source
Energy and Buildings
Volume
303
Issue
Start Page
End Page
PlumX Metrics
Citations
CrossRef : 12
Scopus : 18
Captures
Mendeley Readers : 25
SCOPUS™ Citations
17
checked on Apr 27, 2026
Web of Science™ Citations
20
checked on Apr 27, 2026
Page Views
114
checked on Apr 27, 2026
Downloads
20
checked on Apr 27, 2026
Google Scholar™